Key Advantages of Pll

A rational next-generation power regulator that maintains P-TYPE's proven technology while significantly reducing price

Free Voltage — Wide Voltage Range in One Unit

40 – 130 VAC
Low Voltage Range (LV)
Free Voltage
131 – 480 VAC
High Voltage Range (HV)

Automatically sets the control reference based on the customer's selected voltage, achieving more precise control than competing products.

🎛️

ALL IN ONE CONTROL

Standard voltage/current display and combined control (automatic switching from phase-angle control to zero-crossing control) reduce complexity and improve efficiency.

📡

Convenience Features Built-in

Alarm history, self-diagnostics, PLF tuning, and RS-485 communication are standard. High-end product convenience features are built in for greater ease of use.

💰

Cost-Effective Price

The next-generation product that maintains the proven P-TYPE technology since Korea's first digital power regulator in 2000, while significantly reducing the price.

🛡️

Multiple Alarm Protection

Comprehensive alarm system including overcurrent (OC), overcurrent warning (OCW), heat sink overheat, SCR element fault, partial load failure (PLF), power noise, main power cutoff, load open, fuse open, and load imbalance.

Pll Order Code Configuration

Select the desired specifications according to the code configuration order below.

S/T
↓
①
-
Pll
↓
②
-
220
↓
③
-
D/A/C
↓
④
-
Current
↓
⑤
-
ZC/PA/PZ/PI/PV/PW
↓
⑥
-
F/X
↓
⑦
-
RS/EN/RT
↓
⑧
-
U/X
↓
⑨
-
XX
↓
⑩
① Phase
Input Phase
S — Single-phase
T — Three-phase
② Model
Product Model
Pll — Pll Power Regulator
③ Rated Voltage
Free Voltage Range Selection
LV — Low Voltage (40 ~ 130 VAC)
HV — High Voltage (131 ~ 480 VAC)

Specify voltage: 110, 220, 380, 440 (factory default values; customer may adjust within LV/HV range)
④ Control Power
Device Power Type
D — DC Type (DC 24V)
A — AC Type (AC 110~220V)
C — DC Compact Type (DC 24V)
⑤ Rated Current
Current Capacity
Select from 10A ~ 500A (See specifications)
⑥ Control Method
Output Control Method
ZC — Zero-crossing Control
PA — Phase-angle Control
PZ — Combined Control
PI — Current Feedback
PV — Voltage Feedback
PW — Power Feedback
⑦ Fan
Cooling Fan
F — With Fan
X — Without Fan
⑧ Communication / Output
Communication Option
RS : RS-485
EN : EtherNET option — DC Type PCB power exclusive option
RT : Transmission Output option — AC Type PCB power exclusive option
⑨ UL Certification
International Certification
U — UL Certified Product
X — Not Certified
⑩ Reserved
Reserved
XX

Communication Options by Control Power Type

Available communication and output options vary depending on the selected type.

Control Power Type RS-485 (RS) EtherNET (EN) Transmission Output (RT)
C — DC Compact Type (DC 24V) ● — —
D — DC Type (DC 24V) ● ● —
A — AC Type (AC 110~220V) ● — ●

● Supported · — Not supported · EtherNET is exclusive to D-type · Transmission Output is exclusive to A-type

Pll Product Specifications

ItemSpecifications
Operating VoltageFree Voltage LV: 40 ~ 130 VAC / HV: 131 ~ 480 VAC
Rated Voltage: 110V / 220V / 380V / 440V
Rated Current (CE Certified)10 / 25 / 40 / 55 / 70 / 90 / 110 / 130 / 160 / 200 / 250 / 320 / 400 / 500 A
Rated Current (UL Certified)10 / 25 / 40 / 55 / 70 / 90 / 100 / 130 / 160 / 200 / 250 / 320 / 400 / 500 A
Rated Frequency50 / 60 Hz ± 2%
Load TypeResistive load / Inductive load (Zero-crossing: resistive only)
Minimum Load Current30% of device current capacity
Output Range0 ~ 100%
Control PowerDC Type: DC 24V / AC Type: AC 110 ~ 220V
Power Consumption10 ~ 70A: MAX 19W / 90 ~ 500A: MAX 37W (incl. FAN)
Analog Control Input Signal4 ~ 20mA (Impedance 25Ω)
Analog Control Input ChannelsSingle/Three-phase (Current 1ch, Voltage 1ch)
Output ContactN.O / N.C selectable (2ch, Ic ≤ 2A)
D/I ContactSingle-phase 2ch / Three-phase 2ch
Control MethodPhase / Zero-crossing / Combined / Current Feedback / Voltage Feedback / Power Feedback
Communication / OutputRS-485 or Ethernet (option) / Transmission Output (option)
Cooling MethodDC·AC 40A or less: Natural cooling (option) / AC 55A or more: Forced cooling
Alarm FunctionsOvercurrent (OC), Overcurrent Warning (OCW), Heat sink overheat (OTW/OT: 60/85℃), SCR element fault (SCR), Partial Load Failure (PLF), Power noise (NOS), Main power cutoff (MPF), Load open (LINE), FUSE open (FUSE), Load imbalance (UL — 3-phase only)
Insulation Resistance100 MΩ or more (DC 500V reference)
Operating Temperature0 ~ 40℃
Humidity Range40 ~ 85% RH (no condensation)
Display3 Color FND (3×2 Segment, 8-unit LED, 5-status LED)